Range:
|
Voltage |
: 10~600V |
Current : |
suitable for CT secondary rating (optional)Maximum 6A for 5A ratingMaximum 1.2A for 1A rating |
Triggered trace memory / fault recording range |
V ≤ 600VA ≤ 8 x rated |
Frequency : |
40 – 70Hz |
Burden: |
|
Voltage: |
< 0.4VA at 600V< 0.04VA at 150V |
Current: |
< 0.1VA at 5A |
Overload Capacity |
|
Voltage |
750V continuous1000V 10 seconds1200V 3 seconds |
Current |
2 x rated continuous10 x rated 30 seconds25 x rated 2 seconds
50 x rated 1 seconds |
Monitoring/inputs/outputs |
Measured system |
Suitable for 3 phase 4 wires / 3 phase 3 wires / single
phase 2 & 3 wires / 3 phase balanceSelect by input wiring & software configuration |
Programmability: |
Software accessible / password lockSystem selection : 3 phase 4 wires / 3 phase 3 wires
/1 phase 2 & 3 wires and 3 phase balancePT : 1 – 5000.0 ; CT : 1 – 2000.0 |
Readout display control |
4 digits / auto scan or manual selection / scanning time |
Communication |
Baud rate 1200 / 2400 / 4800 / 9600 / 19200Address setting 1 – 254Calibration : software with password lock
Memory : all of energy date and status setting |
Normal Operation |
250Vac / 30Vdc, 10A resistive250Vac / PF 0.4, 6A inductive30Vdc / t=7ms, 6A inductive |
Interrupting Capacity |
300Vac, 10A250Vdc, resistive 0.32A maximum, t=7ms125Vdc, resistive 0.5A maximum, t=7ms |
Analog Input ( AI ) |
Accuracy, 0.5% fs3 differential analog inputs / process variablesStandard input 4-20mA / 0-20mA
Common mode voltage E100V maximum
Option input 0-10V / 0-5V / 0-1V / 1-5V / 2-10V |
Analog output (AO) |
Accuracy, 0.5% fs4 isolated analog outputsStandard output 4-20mAdc / load ≤ 500Ω
Configurable
Measured parameters
Input range, unipolar / bipolar |
Pulse Output ( PO ) |
2 pulse outputs photo-isolatedConfigurableParameter , WH / VarH / VAH / AH
Unit, ±1WH / ±1QH / 1VAH / 0.01AH
Pulse width / 50% duty cycle |
Standard output: |
4-20mAdc / load < 500Ω |
Configurable Measured parameters |
Input range, unipolar / bipolar |
General Specifications |
Communication ports: |
RS485 ( standard ) ;RS232 ( option )Modbus® RTU protocol |
Display: |
LCD 0.4” display, 3 rows of 8 alphanumerics |
RTC |
Maximum deviation 5 seconds in 24 hoursTime for year / month / day / hour / minute / sec |
Dielectric strength: |
IEC 255-52KV AC rms 1 minute between input / output / power |
Impulse and surge test: |
ANSI/IEEE C37.90.1-1989 (3KV) SWC testIEC 255-22-1 class III SWC testIEC 255-22-4 class IV (IEC 801-4) SWC test
IEC 255-5 1.2 x 50us (5KV) impulse test |
Stability: |
Temperature range -25 to +55°C, maximum 100 ppm/°CLong term stability 0.15% drift maximum per year |
Operating condition: |
Temperature range -25 to +60°C,RH 20 – 95% non-condensed |
Storage condition: |
Temperature range -25 to +60°C,RH 20 – 95% non-condensed |
Power supply: |
AC 80-260V, 40-70Hz, DC 80-330VDC 20-60VDissipation maximum 12VA for AC and 6 Watts for DC |
Mounting / Dimension: |
Panel type mountingDIN 120 x 120 x 130.5mmCut out : 92 x 92mm |