General Specifications |
Accuracy ( 23±3°C ) |
0.07% reading / PF ± 0.03% RO |
Maximum output load |
DC current mode : maximum 10V dropDC voltage mode : maximum 5mA drive |
Output of WH & VarH: |
Open collecter type, maximum 30V / 30mA |
Dielectric strength |
AC 2KV 1 minute between terminals; AC 2.6KV 1 minute / terminals to case |
Surge and impulse test |
ANSI C37.90 / 1989, IEEE-587, 1983 |
Maximum input over: |
Current related input |
|
Voltage related input |
1A / 5A4 x rated / continuous
10 x rated / 10 seconds
50 x rated / 1 second
80 x rated / 0.5 second |
10A2 x rated / continuous
25 x rated / 1 second
50 x rated / 0.5 second |
1.5 x rated / continuous2 x rated / 10 seconds |
Input burden |
Current less 0.2 VA; voltage less 0.1 VA |
Response time & ripple |
≤400 ms for step change 0-99% ripple less 0.5% ro peak to peak |
Frequency |
50 ± 2 Hz; 60 ± 2 Hz; 400 ± 5 Hz ( Watt only ) |
Waveform |
Watt – 2% 3rd, Var – sinusoidal |
Stability |
Temperature range ( 20 to 26°C ) long term stability / year |
Maximum 60 ppm / °C less 0.2% draft / year typically ……. WattsMaximum 70 ppm / °C less 0.2% draft / year typically ……. Vars |
Storage condition |
Temperature range -25 to 70°C, RH 20 to 95% non condensed |
Operating condition |
Temperature range -20 to 65°C, RH 0 to 99% non condensed |
Magnetic field effect |
< 0.01% under 100 ampere turns at 1M center |
Power dissipation |
< 7 VA |